In a pre-engineered building, main frames are made in pieces that fit on a truck and are bolted together on site. The joints between those pieces carry the full bending moment of the frame, so connection design is not a detail to finish at the end. It affects member sizes, fabrication time and erection speed.
This post explains the main connection types in a PEB portal frame and the design ideas behind them, as they apply under IS 800:2007. It is an overview for estimators, sales engineers and owners; the engineer of record designs each connection for the actual forces.
The connections in a portal frame
A typical single-span PEB frame has these joints:
| Connection | Where | What it carries |
|---|---|---|
| Base plate | Column foot to foundation | Axial force, shear, and moment if the base is fixed |
| Knee (haunch) | Column top to rafter | Large negative moment, shear, axial force |
| Rafter splice | Between rafter segments | Moment and shear at that point along the rafter |
| Ridge | Apex, where two rafters meet | Positive moment under gravity, reversal under wind uplift |
| Column splice | Only on tall columns | Moment, axial force, shear |
Secondary connections, such as purlin cleats, girt cleats, bracing gussets and flange braces, carry smaller forces but are far more numerous.
End-plate moment connections
Almost all main frame joints in a PEB are end-plate connections. A plate is welded to the end of each member, and the two plates are bolted together on site. The bolts near the tension flange carry the tension from the moment, the compression flange bears against the other plate, and shear is carried by the bolts through friction or bearing.
Extended and flush end plates
- An extended end plate projects beyond the tension flange, so bolts can sit on both sides of that flange. This gives a stronger, stiffer joint and is common at the knee.
- A flush end plate stays within the depth of the member. It is simpler and used where moments are lower, such as some rafter splices.
What the engineer checks
For an end-plate moment connection, the main checks are:
- Bolt tension in the bolts near the tension flange, including any extra force from prying action when the end plate bends.
- End plate bending, which decides the plate thickness. A thin plate can bend and increase bolt forces through prying.
- Bolt shear from the vertical shear and any axial force.
- Welds between the flanges, web and end plate, sized to develop the forces they carry.
- Column or rafter web and flange at the joint, which may need stiffeners where concentrated forces are high.
- Joint stiffness, because the frame analysis usually assumes the knee is rigid. If the joint is too flexible, the frame deflects more than predicted.
Under IS 800, these checks use the design strength of bolts in tension and shear, the bearing strength of plates, and the combined tension and shear interaction for bolts that carry both. The same ideas appear in AISC 360, with different formulas and resistance factors; see our guide on IS 800 vs AISC 360 for PEB for how the two codes differ.
Bolt grades and pretension
Bolt grades
Bolts are specified by property class. In Indian PEB practice, main frame connections commonly use high strength bolts of property class 8.8 or 10.9, while lighter secondary connections often use lower grade bolts. The first number of the property class relates to the tensile strength and the second to the ratio of yield to tensile strength. The drawings must state the grade, diameter, length and any washer requirement for every joint.
Bearing type and friction type
IS 800 recognises two ways a bolted joint carries shear:
- Bearing type: the plates can slip slightly until the bolt shank bears on the hole. Simple, but some slip happens under load.
- Friction type (slip critical): high strength bolts are pretensioned, clamping the plates together so that friction carries the shear without slip. The slip resistance depends on the bolt pretension, the number of friction surfaces and the surface condition of the plates.
Why pretension matters
Pretensioning bolts in a moment connection makes the joint stiffer and reduces the risk of loosening under wind-induced load reversal and vibration. Pretension is applied by a controlled method, such as a calibrated torque wrench or turn-of-nut tightening, as specified by the engineer. If the design assumes pretensioned bolts, the erection drawings and method statement must say so clearly, and site teams need the right tools. A bolt that is designed as pretensioned but tightened by hand does not behave as designed.
Flange bracing
The inner flange of a PEB rafter or column goes into compression in some load cases, for example the bottom flange of the rafter near the knee under gravity, or along much of the rafter under wind uplift. The purlins and girts brace only the outer flange.
Flange braces are small angles or cold-formed members running diagonally from a purlin or girt to the inner flange. They restrain that flange against lateral-torsional buckling and reduce its unbraced length. Their spacing is a design input for the member check: if the drawings show a flange brace at every second purlin, the site must install it there. Missing flange braces are one of the most common site errors in PEBs, and they directly reduce the capacity of the frame.
Base plates and anchor bolts
Pinned bases
Many PEB frames use pinned bases: a base plate with a small number of anchor bolts placed near the column centre, designed for axial load and shear but not significant moment. Pinned bases keep foundation sizes down but give a more flexible frame.
Fixed bases
Fixed bases use a larger plate and more anchor bolts placed away from the centre so they can resist moment. They reduce frame sway and are common where cranes run or columns are tall. The foundation must then be designed for the base moment.
What the base plate design covers
- Bearing pressure on the concrete or grout under the plate.
- Plate thickness, from bending of the plate between the column flanges and beyond them.
- Anchor bolt tension, from uplift and moment, and their embedment and anchorage into the concrete.
- Shear transfer, through friction, anchor bolts or a shear key under the plate.
- Grout thickness and quality, which must be specified on the drawing.
The base condition used in the frame model must match the detail shown on the anchor bolt plan. A frame analysed as fixed but built with a pinned detail will sway more than designed.
Standardise to save time
A building with fifty unique connections is slow to detail, fabricate and erect. Most PEB frames can be covered by a small family of standard end plates and bolt patterns, with only special frames needing special joints. This is one of the cost levers in our post on how to reduce PEB steel cost.
Connection design follows from the frame analysis, so it is only as good as the forces behind it. Whatever software you use, the engineer of record checks the connection design and approves the details on the drawings.
Frequently asked questions
Which bolts are used in PEB connections?
Moment connections in PEB frames normally use high strength friction grip bolts of property class 8.8 or 10.9. Lighter secondary connections such as purlin and girt cleats commonly use lower grade bolts. The engineer specifies the grade, diameter and whether the bolts are pretensioned.
What is the difference between a bearing type and a slip critical connection?
In a bearing type connection the bolts carry shear by bearing against the plates after a small slip. In a slip critical connection the bolts are pretensioned so that friction between the plates carries the load without slip. Slip critical joints are used where slip is not acceptable, for example under reversing or fatigue loads.
How does the base condition change the base plate and anchor bolt design?
Many PEB frames use pinned bases because they keep foundation sizes down. Fixed bases are used where sway must be limited, for example with cranes or tall columns. The base plate, anchor bolts and foundation must be designed for the base condition assumed in the frame analysis.