Deflection limits for PEB: rafters, frame drift, purlins, girts and cranes

Strength keeps a building standing. Deflection decides whether the roof leaks, the walls crack and the crane runs straight, so it often decides the steel too.

16 NOVEMBER 2026 · 7 MIN READ

A pre-engineered building is light and flexible by design. Tapered frames put steel only where the bending moment needs it, and that efficiency means stiffness, not strength, often controls the member sizes. A frame that passes every strength check can still sag enough to pond water, sway enough to crack a brick wall, or move enough at crane level to make the crane bind.

This post explains the serviceability checks that matter in a PEB and how to agree on them with the client.

Where the limits come from

IS 800:2007 contains a table of recommended deflection limits. It is organised by building type (industrial buildings and others), by member (purlins, girts, rafters, gantry girders, columns) and by the kind of finish the member supports. Each limit is written as a fraction of the span or height, for example span divided by a number. Two features of the table matter in practice:

  • Elastic versus brittle cladding. For the same member, the limit is more relaxed when it supports elastic cladding such as metal sheeting, and stricter when it supports brittle finishes such as masonry, plaster or glazing.
  • Crane girders have their own, much tighter limits that depend on the type and capacity of the crane.

The table gives recommended values. The code allows other limits where the client or the use demands, and many international clients bring their own. Always read the limits from the code and record which ones the design uses.

IS 800:2026 keeps these deflection limits, apart from a looser limit on the relative displacement of crane rails; see IS 800:2026 vs IS 800:2007.

Loads for serviceability checks

Deflections are checked with unfactored loads. IS 800 Table 4 includes serviceability combinations in which the load factors are one. In practice:

  • Vertical deflection of rafters and purlins is checked under imposed (live) load, and often under dead plus imposed load where the finish is sensitive to total sag.
  • Lateral drift of frames and girt deflection are checked under wind load, and under seismic load to IS 1893 for drift.
  • Crane runways are checked under the crane wheel loads, with and without impact as the design basis states.

Checking deflection under factored loads makes the building heavier for no reason. Checking it under dead load alone, for a roof that will carry services and maintenance, makes it too flexible.

Rafter vertical deflection

The main frame rafter deflects most at the ridge (for a single span) or at mid-span of each bay (for multi-span frames). Large rafter deflection causes:

  • Ponding on low-slope roofs, where water collects in the sag and adds more load.
  • Damage to false ceilings, partitions and sprinkler lines hung from the roof.
  • Visible sag in long-span buildings, which worries owners even when the structure is safe.

A gentle roof slope, typical of PEBs, increases the ponding risk. If the roof slope is very low or the gutter is internal, check that the deflected shape still drains.

Rafter deflection can be reduced by deeper sections at mid-span, a stiffer knee or a change in frame type (adding an interior column or a multi-span arrangement). A deeper web is usually the most efficient fix, which is one reason serviceability shapes the tapered profile in tapered frame design.

Lateral drift of frames

Under wind, a portal frame sways. The drift at eaves level is limited as a fraction of the column height. The limit depends again on the cladding:

  • Metal sheeting on the walls: a more relaxed limit, since the sheeting moves with the frame.
  • Masonry or block walls tied to the columns: a much stricter limit, because the wall cracks at small movement.
  • Glazed walls or curtain walls: tight limits set by the glazing system.

In a PEB with brick walls up to a dado height and sheeting above, the critical movement is at the top of the brick wall, not at the eaves. Check drift at that level against the brittle limit, or detail a movement joint between the wall and the column so the frame can move freely.

Drift under seismic load is checked separately to IS 1893, using its own limit on storey drift.

Purlins and girts

Purlins and girts are cold-formed Z or C sections spanning between frames. Their deflection limits come from the same table. Points to watch:

  • Purlin deflection under imposed load affects the sheeting laps and fasteners. Excessive sag leads to leaks at end laps.
  • Girt deflection under wind affects wall sheeting and especially any windows, louvres or doors framed into the girts.
  • Lapped or continuous purlins are stiffer than simple spans; make sure the analysis model matches the lap detail used on site.
  • Sag rods reduce weak-axis deflection and help stability, but do not change strong-axis sag.

Crane runways

Crane girders need the tightest limits in the building. IS 800 gives:

  • A vertical deflection limit for the crane girder that becomes stricter as crane capacity and duty increase.
  • A lateral deflection limit for the girder under surge.
  • A limit on the relative lateral movement between the two crane rails, which controls the frame sway at crane level.

The rail-to-rail movement often controls the main column size in a crane building, because the whole frame must stay stiff under the crane surge and wind together. See crane loads in PEB for the loads behind these checks.

Why limits differ between suppliers

Two suppliers can quote the same building at different weights partly because they use different deflection limits. One may check drift against the elastic-cladding value while the other uses a stricter value for an assumed brick wall. One may check rafter deflection under live load only, the other under dead plus live. Neither is wrong if it matches the brief, but the comparison is unfair if the brief is silent.

When you compare quotes or review a design, ask for the deflection limits used, the load case for each, and the cladding assumption. Our guide on IS 800 vs AISC 360 for PEB also covers how limits differ between the two codes.

How to discuss limits with a client

Clients rarely ask about deflection until something goes wrong. A short conversation at the start avoids that:

  1. Ask what the walls are made of up to what height, and whether glazing is planned.
  2. Ask what hangs from the roof: false ceiling, sprinklers, ducts, conveyors.
  3. Ask about the crane class and how often it runs.
  4. Explain the trade-off in plain words: stiffer means heavier, and the code values are a reasonable default for metal-clad sheds.
  5. Write the agreed limits in the design basis with the load case for each.

Ganithva lists the deflection limit and governing case next to each member check so the engineer can see why a section is the size it is; the engineer still approves the limits and every change. Whatever tool you use, make the limits visible to the client before the drawings are issued.

Checklist

  • Read the limits from the IS 800 table for the member and cladding type.
  • Use unfactored loads in serviceability combinations.
  • Check drift at the top of any brittle wall, not just at eaves.
  • Match the purlin model to the lap detail.
  • Apply crane girder and rail movement limits for crane buildings.
  • Record every limit and load case in the design basis.

Frequently asked questions

Where are the deflection limits for steel buildings in Indian codes?

IS 800:2007 has a table of recommended deflection limits for different building types and members, including industrial buildings, purlins, girts, crane girders and columns. The limits are expressed as a fraction of span or height and depend on whether the cladding is elastic or brittle.

Why do limits depend on the cladding?

Metal sheeting can bend and move with the frame without damage, so it tolerates larger deflections. Brittle finishes such as masonry, plaster or glazing crack at much smaller movements, so the frame must be stiffer where it supports them.

Are deflections checked with factored loads?

No. Deflection is a serviceability check and uses unfactored (characteristic) loads, with the load factors set to one in the serviceability combinations.

Can a client ask for tighter limits than the code?

Yes. The code limits are recommendations. A client with sensitive equipment, a brittle wall finish or a busy crane can specify tighter limits, and the design basis should record them because they change the steel weight.