# IS 875 Part 3 wind load calculation for a PEB

How to work out wind load on a pre-engineered building under IS 875 (Part 3):2015, from basic wind speed to net pressures on the frame, with a worked example.

PUBLISHED · 16 NOVEMBER 2026

**Key points**

- IS 875 Part 3:2015 wind load on a PEB is worked out in a fixed order: Vz = Vb·k1·k2·k3·k4, then pz = 0.6 Vz², then pd = Kd·Ka·Kc·pz, and net pressure = (Cpe − Cpi)·pd.
- Under IS 875 Part 3:2015 the design wind pressure pd must not be taken less than 0.7 pz, and the directionality factor Kd is 0.90 for buildings but 1.0 in cyclone-affected regions.
- The IS 875 Part 3 area averaging factor Ka is 1.0 for tributary areas of 10 m² or less, 0.9 at 25 m² and 0.8 at 100 m² or more, so purlins and sheeting see higher pressure than main frames.
- The IS 875 Part 3 internal pressure coefficient Cpi is ±0.2 for walls with little permeability, ±0.5 for medium openings and ±0.7 for large openings, and both signs must be checked as separate load cases.
- A PEB frame model needs wind cases normal to the ridge from both sides and parallel to the ridge, each with positive and negative Cpi, plus extra cases for any dominant openings.

## The method in one line

Wind usually decides a pre-engineered building: the roof is light, so uplift can exceed dead load and reverse the frame forces. The calculation in IS 875 (Part 3):2015 runs in a fixed order:

**Vb → Vz = Vb·k1·k2·k3·k4 → pz = 0.6 Vz² → pd = Kd·Ka·Kc·pz → net pressure = (Cpe − Cpi)·pd**

Each step is explained below. Always read the factor values from the code itself for your site and geometry; the values used in the example are for that example only.

## Basic wind speed Vb

The basic wind speed is read from the wind speed map in the code, with a list of values for major cities given in an annex. It is a 3-second gust speed at 10 m above ground in open terrain, for a 50-year return period. Indian values range from 33 m/s to 55 m/s; most industrial locations fall between 39 m/s and 50 m/s.

Check the location carefully: a site a few kilometres from a listed city can fall in a different zone on the map.

## Factors k1, k2, k3 and k4

### k1, risk coefficient

k1 adjusts for design life. It is 1.0 for general buildings with a 50-year design life; the code tabulates other values, which depend on Vb, for temporary and for longer-life structures.

### k2, terrain roughness and height factor

k2 accounts for ground roughness and height. The 2015 code has four terrain categories, from open sea coasts and flat treeless plains (category 1) to dense city centres (category 4); the choice must reflect the actual upwind terrain in each wind direction. For low PEBs the roof height is usually used. For category 2 at 10 m, k2 = 1.00; rougher terrain gives lower values and greater height higher ones.

### k3, topography factor

k3 is 1.0 on flat or gently sloping ground and increases near hills, ridges, cliffs and escarpments, by a procedure given in the code.

### k4, importance factor for cyclonic regions

k4 applies only in the cyclone-prone coastal regions defined in the code. It is 1.0 for general buildings, 1.15 for industrial structures and 1.30 for structures of post-cyclone importance such as hospitals and emergency shelters. Outside those regions, k4 = 1.0.

## Pressure pz and design pressure pd

The design wind speed is Vz = Vb·k1·k2·k3·k4, and the wind pressure at height z is:

**pz = 0.6 Vz²** (pz in N/m², Vz in m/s)

The 2015 code then reduces pz with three factors to get the design wind pressure:

**pd = Kd · Ka · Kc · pz**, and pd must not be less than 0.7 pz.

- **Kd, wind directionality factor.** Accounts for the low chance of the strongest wind coming from the worst direction. It is 0.90 for buildings, but must be taken as 1.0 in cyclone-affected regions.
- **Ka, area averaging factor.** Gusts do not hit a large area all at once, so larger tributary areas get a smaller factor: 1.0 for 10 m² or less, 0.9 at 25 m² and 0.8 at 100 m² or more, interpolating between. A main frame has a large tributary area; a purlin or a sheet fixing has a small one.
- **Kc, combination factor.** Allows a reduction when a member receives wind from several surfaces (for example roof and walls together) whose peak pressures do not occur at the same moment. Values are tabulated in the code for different framing cases. Where in doubt, Kc = 1.0 is conservative.

## Pressure coefficients Cpe and Cpi

### External coefficients, Cpe

Cpe depends on the surface (windward wall, leeward wall, side walls, windward and leeward roof slopes), the building's height-to-width and length-to-width ratios, the roof angle and the wind direction (normal to or parallel to the ridge). The code tabulates Cpe for rectangular clad buildings and pitched roofs. For roof angles between tabulated values, interpolate. Separate, more severe local coefficients apply near roof edges, ridges and wall corners; these are for cladding, purlins and fixings, not for main frames.

### Internal coefficients, Cpi

Cpi depends on how open the walls are:

| Openings in walls | Cpi |

| Little permeability (openings up to about 5% of wall area) | ±0.2 |
| --- | --- |
| Medium openings (about 5% to 20%) | ±0.5 |
| Large openings (above 20%) | ±0.7 |

A large door on one wall that may be open in a storm is a dominant opening and needs specific treatment. Positive Cpi pushes outward on every inside surface, increasing roof uplift; negative Cpi pulls inward. Both signs must be checked.

The net pressure on a surface is (Cpe − Cpi) × pd, with positive values acting towards the surface.

## Worked example

A warehouse near Hyderabad: 30 m wide, 60 m long, eave height 8 m, roof slope 1 in 10 (about 5.7°), ridge height 9.5 m, frames at 7.5 m centres, flat open site, terrain category 2, not in a cyclone-prone region, wall openings below 5%.

| Step | Value | Note |

| Vb | 44 m/s | Hyderabad, from the code's list of cities |
| k1 | 1.0 | General building, 50-year life |
| k2 | 1.00 | Category 2, height up to 10 m |
| k3 | 1.0 | Flat ground |
| k4 | 1.0 | Not cyclone-prone |
| Vz | 44 m/s | 44 × 1.0 × 1.00 × 1.0 × 1.0 |
| pz | 1161.6 N/m² | 0.6 × 44² |
| Kd, Ka, Kc | 0.9, 0.8, 1.0 | Main frame, tributary area well over 100 m², Kc taken conservatively |
| pd | 836.4 N/m² | 0.9 × 0.8 × 1.0 × 1161.6; above 0.7 pz = 813.1, so 836.4 governs |

The building has h/w = 8/30 ≈ 0.27 and l/w = 60/30 = 2. For wind normal to the ridge, take illustrative coefficients for a low building of these proportions: windward wall +0.7, leeward wall −0.25, windward roof slope −0.9 and leeward roof slope −0.4 (the roof values are for 5°; at 5.7° interpolate towards the 10° values). With Cpi = ±0.2 and a 7.5 m bay, the table shows the worse sign of Cpi for each surface. In the frame model each load case uses one Cpi value on all surfaces at once, so the two Cpi signs become two separate load cases.

| Surface | Cpe − Cpi | Net pressure | Line load on frame |

| Windward wall (Cpi −0.2) | +0.9 | +0.753 kN/m² | 5.65 kN/m inward |
| Leeward wall (Cpi +0.2) | −0.45 | −0.376 kN/m² | 2.82 kN/m outward |
| Windward roof (Cpi +0.2) | −1.1 | −0.920 kN/m² | 6.90 kN/m uplift |
| Leeward roof (Cpi +0.2) | −0.6 | −0.502 kN/m² | 3.76 kN/m uplift |

Compare the windward roof uplift of 6.90 kN/m with the frame's dead load per metre. With light sheeting, purlins and frame, uplift is usually well above dead load, so the rafter bottom flange goes into compression and the flange braces become critical. That is why wind often governs both strength and the bracing layout; see [PEB optimization](https://ganithva.com/guides/peb-optimization) for how this feeds into sizing.

For purlins and sheeting in the same building, the tributary area is small, so Ka = 1.0 and pd = 0.9 × 1161.6 = 1045.4 N/m², before the higher local edge and corner coefficients are applied.

## Load cases for the frame

For a typical gable building, set up at least these wind cases on the frame model:

- Wind normal to the ridge (from the left and from the right), each with Cpi positive and negative.
- Wind parallel to the ridge, with Cpi positive and negative. The frame sees mainly roof suction and side wall suction in this direction, and the end walls and bracing take the longitudinal force.
- Extra cases for dominant openings, if any.

The combination factors differ between IS 800 and AISC 360; see [IS 800 vs AISC 360 for PEB](https://ganithva.com/guides/is-800-vs-aisc-360-peb). If you build the model in STAAD.Pro, the [PEB design in STAAD.Pro guide](https://ganithva.com/guides/peb-design-in-staad-pro) covers applying these as member loads.

## FAQ

### What is the formula for design wind pressure in IS 875 Part 3?

The design wind speed is Vz = Vb × k1 × k2 × k3 × k4. The wind pressure is pz = 0.6 Vz² in N/m², with Vz in m/s. The design wind pressure is pd = Kd × Ka × Kc × pz, and pd must not be taken less than 0.7 pz.

### What value of Cpi should be used for a PEB?

It depends on the openings. For buildings with little permeability the code uses ±0.2, for medium openings ±0.5, and for buildings with large openings a higher value, with dominant openings treated separately. Both the positive and the negative value must be checked, because each can govern a different member.

### When does k4 apply?

The importance factor for cyclonic regions, k4, applies only to sites in the cyclone-prone coastal regions the code identifies. Elsewhere it is 1.0. In those regions it is 1.0 for general buildings and higher for industrial structures and for buildings needed after a cyclone.

### Why is the pressure on purlins and sheeting higher than on the frames?

Two reasons. Small members have a small tributary area, so the area averaging factor Ka is 1.0 instead of a reduced value, and roof edges, corners and ridges have higher local suction coefficients that apply to cladding and its fixings but not to the main frame.

### Does IS 875 Part 3:2015 replace the 1987 edition?

Yes. The 2015 revision introduced the wind directionality factor Kd, the area averaging factor Ka and the combination factor Kc, revised the terrain categories and the k2 values, and added the cyclonic importance factor k4. Older calculations made to the 1987 edition should not be reused without checking.

Ganithva works out IS 875 (Part 3) wind loads and IS 1893 seismic loads for a PEB from the project brief, and the engineer checks and approves them before they go into the model. See [PEB design software](https://ganithva.com/peb-design-software), or [book a walkthrough](https://ganithva.com/contact).