title: "Z vs C purlins and girts in PEB: lapping and sag rods"
description: "Z vs C purlins and girts for PEB buildings: lapping and continuity, sag rods, flange braces, spacing and the cold-formed design checks in Indian practice."
url: https://ganithva.com/blog/purlins-and-girts-z-vs-c-sections
---

# Z vs C purlins and girts in PEB buildings: what changes and why

Purlins and girts are the lightest members in a PEB, but there are a lot of them. Choosing between Z and C sections, and detailing them well, has a direct effect on tonnage and on how the frame behaves.

16 NOVEMBER 2026 · 7 MIN READ

**Key points**

- Z sections dominate PEB roof purlins because slightly different sizes nest at the supports and can be lapped over the rafters, forming a continuous beam with lower moment and deflection than a simply supported C purlin.
- C sections are used in PEBs where a member spans one bay or needs a flat back face, such as eave struts, framed openings, door and window jambs and headers, and short end bays.
- Sag rods tie PEB purlins together along the slope, carry the down-slope load to the ridge or eave, and reduce the unbraced length of the bottom flange, which is in compression under wind uplift.
- PEB purlins and girts also restrain the main frame through flange braces to the inner flange, so moving a purlin line or leaving out a flange brace on site can invalidate the rafter design.
- In India, cold-formed purlins and girts are covered by IS 801 and IS 811, and many designers also check them to AISI S100, which treats local and distortional buckling in more detail.

In a pre-engineered building the main frames get most of the attention, but the **secondary members** do a lot of work. **Purlins** span between rafters and carry the roof sheeting. **Girts** span between columns and carry the wall cladding. Together with the eave struts they also restrain the main frame flanges and act as struts in the bracing system. Get them wrong and the roof sags, the walls rattle, or the main frame loses the restraint its design assumed.

Almost all PEB purlins and girts are **cold-formed** from galvanised or coated high-strength coil, rolled into Z or C profiles with lips on the flanges. This post explains the difference between the two shapes and the details that decide how they perform.

## Z and C sections at a glance

| Feature | Z section | C section |

| Shape | Flanges point in opposite directions | Both flanges point the same way |

| Lapping over supports | Yes, sections nest inside each other | Not by nesting; joined by sleeves or butted |

| Typical structural action | Continuous over several bays | Simple span between supports |

| Principal axes | Inclined to the web | Parallel to the web |

| Twisting under load | Tends to deflect sideways under vertical load | Tends to twist, as the shear centre is outside the web |

| Typical use | Roof purlins, long wall girts | Eave struts, openings, jambs, short bays |

## Why Z sections dominate PEB roofs

### Lapping gives continuity

The big advantage of a Z section is that a slightly larger and a slightly smaller Z can **nest** together. At each rafter the purlins from adjacent bays overlap for a set distance and are bolted through both webs. The run of purlins then acts as a continuous beam rather than a chain of simple spans.

Continuity matters because:

- the peak moment moves to the supports, where the lap doubles the section,

- the mid-span moment and deflection fall compared with a simply supported member,

- end bays can be given a thicker section or a longer lap, since the end span of a continuous beam sees higher moments.

The lap length is normally set as a proportion of the bay on each side of the support, and the manufacturer’s tested lap details should govern the design. The lap must be long enough to develop continuity and must have enough bolts to transfer moment between the two sections. A short or under-bolted lap behaves more like a hinge than the design assumed.

### Inclined principal axes

A Z section’s principal axes are tilted relative to its web. A purely vertical load therefore makes the purlin move both down and sideways. On a sloping roof this combines with the down-slope load component. In practice the sideways movement is controlled by the sheeting fastened to the top flange, by sag rods, and by the anti-roll details at the rafters. The design must account for this; it is not an error to be ignored.

## Where C sections fit

C sections cannot nest in the same way, so a C purlin is usually designed as **simply supported** between frames, or spliced with a sleeve. That makes it heavier than a lapped Z over the same bay. C sections are still the right choice where:

- the member only spans one bay, such as at a framed opening or a short end bay,

- a flat back face is needed, for door and window jambs and headers,

- the member must sit flush against something, like the **eave strut** at the top of the side wall,

- two sections are placed back to back to make a stronger built-up member.

A C section’s shear centre lies outside the web, so a load on the flange tries to twist it. Restraint from the sheeting and sag rods controls this, just as it controls the sideways movement of a Z.

## Sag rods and bridging

Purlins are deep and stiff about their major axis but very flexible about the minor axis. On a sloped roof part of the load acts down the slope, along the weak axis. **Sag rods** (or angle bridging) connect the purlins along the slope and carry this component to the ridge or the eave, where it is resolved. They split the weak-axis span into shorter lengths.

Sag rods also help when the wind lifts the roof. Under uplift the **bottom flange** of the purlin is in compression, and that flange is not fastened to the sheeting. Lines of sag rods or bridging reduce its unbraced length. The number of lines per bay depends on the bay length, the roof slope, the purlin size and the uplift; it comes out of the design, not from a fixed rule.

Wall girts need the same thinking. A girt carries wind pressure and suction about its major axis and the self-weight of the cladding about its minor axis. Sag rods in walls hang the girts from the eave strut so they do not sag between columns.

## Flange braces: a job for the purlins

Here is the part that is easy to forget. Purlins and girts are also **restraints for the main frame**.

The outer flange of a rafter or column is held by the purlins or girts fastened to it. The **inner flange** is free. Under wind uplift, or near the knee under gravity load, that inner flange goes into compression and can buckle sideways. **Flange braces**, small angles from the purlin or girt down to the inner flange, provide the restraint.

This means:

- moving a purlin line changes the unbraced length of the rafter,

- leaving out a flange brace on site can invalidate the rafter design,

- the purlin must be strong and stiff enough to provide the brace force, which is a check of its own.

The same purlins also act as struts in the roof bracing system. See [bracing in PEB buildings](https://ganithva.com/blog/bracing-in-peb-buildings) for that load path.

## How purlin and girt spacing is chosen

There is no single correct spacing. It is chosen from:

- **Sheeting capacity.** The roof or wall sheet must span between purlins or girts under the design wind pressure and suction, and under the roof imposed load. Check the sheet manufacturer’s span tables for the profile and thickness.

- **Purlin capacity.** Wider spacing means more load on each purlin, so a deeper or thicker section. Closer spacing means more pieces and more fasteners.

- **Wind zones on the roof.** IS 875 Part 3 gives higher local suction near eaves, ridges and corners. Purlins are often closer together in those zones, or locally thicker. Our guide to [IS 875 Part 3 wind load for PEB](https://ganithva.com/guides/is-875-part-3-wind-load-peb) covers how these zones are set.

- **Flange bracing needs.** The main frame design may ask for restraint at particular points, which fixes some purlin or girt positions.

- **Openings and services.** Doors, windows, louvres, skylights and solar panel rails all need framing that fits the girt or purlin grid.

The best spacing is usually the one that keeps the total weight of sheeting supports low while using a small number of standard sections. That is a trade-off worth running for every job, because purlins and girts make up a meaningful share of building weight. Our guide to [PEB steel take-off and tonnage estimation](https://ganithva.com/guides/peb-steel-take-off-tonnage-estimation) shows how secondary steel is counted.

## Design checks for cold-formed members

Cold-formed sections are thin, so the checks differ from hot-rolled members:

- **Local and distortional buckling** of the flanges, lips and web reduce the effective section.

- **Lateral-torsional buckling** depends on the restraint from sheeting, sag rods and flange braces.

- **Web crippling** at supports and at concentrated loads.

- **Combined bending and shear** at the laps.

- **Deflection** under imposed load and wind, to keep the sheeting watertight.

In India IS 801 and IS 811 apply to cold-formed light gauge sections. Many designers also check purlins to AISI S100, which handles distortional buckling in more detail. Whichever is used, state it in the design basis so that the checking engineer knows which rules apply.

## Frequently asked questions

### Why are Z purlins preferred for roofs in PEB buildings?

Z sections of slightly different sizes can nest inside each other at the supports, so they can be lapped over the rafters to form a continuous beam. Continuity lowers the bending moment and the deflection compared with a simply supported C purlin, so Z purlins are usually lighter over the typical PEB bay.

### Where are C sections used instead of Z sections?

C sections are used where a member runs over a single bay or needs a flat back face: eave struts, framed openings, door and window jambs and headers, short bays, and members at the ends of runs. They are also easier to connect back to back.

### What do sag rods do in a PEB roof?

Sag rods tie the purlins together along the roof slope and carry the down-slope component of load to the ridge or eave, so the purlins do not bend about their weak axis over the full bay. They also help restrain the purlin flanges against lateral movement.

### Which code is used to design cold-formed purlins in India?

IS 801 covers the design of cold-formed light gauge steel members and IS 811 covers the sections. Because IS 801 is an old standard, many designers also check purlins and girts with the AISI S100 specification, which treats local and distortional buckling in more detail.