title: "Load combinations for PEB to IS 800: a full guide"
description: "Limit state load combinations for pre-engineered buildings to IS 800 Table 4 and IS 875 Part 5: gravity, wind uplift with 0.9 dead load, cranes and seismic."
url: https://ganithva.com/blog/load-combinations-for-peb-is-800
---

# Load combinations for PEB to IS 800: gravity, wind uplift, cranes and seismic

A PEB is rarely governed by one load. It is governed by the worst combination, and missing one case, usually uplift, is the most common design error.

16 NOVEMBER 2026 · 8 MIN READ

**Key points**

- A complete PEB load combination set to IS 800 covers gravity, wind with full and reduced dead load, crane, seismic and serviceability cases; the most commonly missed case is wind uplift with reduced dead load.
- IS 800 Table 4 uses a dead load factor of 0.9 where dead load reduces the effect being checked, such as wind uplift or overturning, because overestimating the dead load would be unsafe.
- The 0.9 DL + 1.5 WL uplift combination governs PEB purlins under suction, the rafter bottom flange near the knee, anchor bolts in tension and foundations for uplift and overturning.
- Wind and earthquake loads are never combined with each other in PEB design; each is combined separately with dead, imposed and crane loads.
- PEB deflection and drift are checked in separate serviceability combinations with unfactored loads, such as DL + LL or LL for rafters and purlins and WL alone for frame drift.

Load combinations are where a pre-engineered building design is won or lost. The individual loads may be correct, but if the combination set misses the case that governs a member, that member is undersized. In PEBs the missed case is almost always **wind uplift with reduced dead load**, followed by **crane combinations** and the **longitudinal direction**.

This post explains how to build a complete combination set for a PEB using the limit state method of **IS 800:2007**, with load concepts from **IS 875 (Part 5)** and the seismic rules of **IS 1893 (Part 1)**. IS 800:2026 keeps the same load factors; its main changes are in member checks, seismic design and the second-order check, summarised in [IS 800:2026 vs IS 800:2007](https://ganithva.com/blog/is-800-2026-what-changes-for-peb).

## The basic load cases

Before combining, define each primary load case separately:

| Symbol | Load case | Source |

| DL | Dead load: self-weight, sheeting, purlins | IS 875 (Part 1) |

| CL | Collateral load: services, ceiling, solar | Project design basis |

| LL | Roof imposed load | IS 875 (Part 2) |

| WL | Wind load, several directions and internal pressure cases | IS 875 (Part 3) |

| EL | Seismic load, two horizontal directions | IS 1893 (Part 1) |

| CR | Crane vertical, surge and braking | IS 875 (Part 2), IS 807 |

| TL | Temperature, if the building is long without expansion joints | IS 875 (Part 5) |

Keep them as separate primary cases in the analysis model. Combining in the model rather than by hand lets you trace which case governs each member.

## Partial safety factors in IS 800 Table 4

IS 800 Table 4 gives the partial safety factors for loads in the limit state of strength and the limit state of serviceability. The structure of the table is:

- **Dead load + imposed load**: both with the higher factor of 1.5.

- **Dead load + imposed load + wind or seismic**: all three with a reduced factor of 1.2, because the chance of all reaching their full values together is lower.

- **Dead load + wind or seismic**: wind or seismic at 1.5, with dead load at 1.5 where it adds to the effect and **0.9 where it reduces the effect**.

- **Crane loads** are treated as imposed loads, with separate factors for the leading and accompanying imposed load where more than one acts.

- **Serviceability**: factors of one on all loads, with some reduction for accompanying loads.

Read the exact values and the crane rows from the code. The pattern above is what matters for setting up the set.

## Gravity combinations

The basic gravity combination is factored dead plus collateral plus roof live load. It governs:

- The rafter at the knee and ridge in many low-wind regions.

- The purlins under downward load.

- The column base in compression.

Use the full collateral load here. If the roof has areas with different live loads, such as a plant platform, include them as separate cases rather than averaging.

## Wind combinations and uplift

Wind on a PEB is not one load case. IS 875 (Part 3) leads you to several:

- **Wind directions**: at least wind across the building (0°) and along it (90°). For non-symmetric buildings, check the opposite directions too.

- **Internal pressure**: positive (pressure inside) and negative (suction inside). The magnitude depends on the opening ratio of the walls. A building with large doors that may be open in a storm needs the higher internal pressure.

- **Local pressure zones** near eaves, ridges and corners for purlins, girts and sheeting.

Each wind case combines with dead load in two ways:

- **1.5 DL + 1.5 WL** for effects where wind adds to gravity.

- **0.9 DL + 1.5 WL** for **uplift**, where wind lifts the roof and dead load holds it down.

The uplift case is the one that governs:

- **Purlins** under suction, where the unbraced bottom flange is in compression.

- **Rafter bottom flange** near the knee, which is in compression under uplift and needs flange braces.

- **Anchor bolts** in tension.

- **Foundations** for uplift and overturning.

Collateral load should usually be left out of the uplift case, or only a part included, because services can be removed. Record your choice. More on wind cases in our [IS 875 Part 3 wind load guide](https://ganithva.com/guides/is-875-part-3-wind-load-peb).

## Combined gravity and wind

The combination **1.2 DL + 1.2 LL + 1.2 WL** covers cases where live load and wind act together. It rarely governs a plain shed but can govern buildings with mezzanines or significant imposed loads on frames.

## Crane combinations

For crane buildings, add combinations with:

- **Crane vertical loads with impact**, with the crab at each side to produce maximum and minimum wheel loads on each column.

- **Surge** acting with the vertical load, in both directions.

- **Longitudinal braking** with the vertical load, for the bracing and crane-level members.

- **Crane with wind**, at reduced factors, since a crane may operate in moderate wind.

- **Multiple cranes**, where the runway layout allows two cranes near the same frame.

Crane positions multiply the number of combinations quickly. Use the positions that produce maximum effect on each frame rather than every possible position. See [crane loads in PEB](https://ganithva.com/blog/crane-loads-in-peb) for the loads themselves.

## Seismic combinations

IS 1893 (Part 1) and IS 800 Table 4 give the seismic combinations:

- **1.5 (DL ± EL)** and **1.2 (DL + LL ± EL)**, using the imposed load fraction allowed for seismic weight.

- **0.9 DL ± 1.5 EL**, the reduced dead load case, for uplift and overturning.

Seismic is applied in both horizontal directions. Where members resist forces from both directions, IS 1893 requires the orthogonal effects to be combined: full seismic in one direction with a fraction in the other. Wind and seismic are never combined with each other. The inputs for EL are covered in [IS 1893 seismic load for PEB](https://ganithva.com/blog/is-1893-seismic-load-for-peb).

## Serviceability combinations

Deflection and drift checks use unfactored loads:

- **DL + LL** or **LL** alone for rafter and purlin vertical deflection.

- **WL** alone for frame drift and girt deflection.

- **Crane loads** for runway deflection.

Using strength combinations for these checks makes the design heavier without reason. See [deflection limits for PEB](https://ganithva.com/blog/deflection-limits-for-peb).

## Building the set: a numbered procedure

- Define all primary load cases separately in the model.

- Write the gravity combinations.

- For each wind direction and internal pressure case, write the 1.5 DL and 0.9 DL versions.

- Add combined gravity and wind cases.

- Add crane combinations for each crane position, with surge and braking.

- Add seismic combinations in both directions, including the 0.9 DL case.

- Add serviceability combinations with factors of one.

- Run the analysis and list the governing combination for each member.

If you work in STAAD.Pro, the [PEB design in STAAD.Pro guide](https://ganithva.com/guides/peb-design-in-staad-pro) shows how to organise primary cases and combinations so the governing case is easy to trace.

## Common mistakes

- **No 0.9 DL uplift case**, leaving purlins, flange braces and anchors undersized.

- **One internal pressure case only**, usually the positive one.

- **No longitudinal wind or seismic** for the bracing.

- **Crane surge in one direction only.**

- **Collateral load in the uplift case**, which overstates the restoring load.

- **Serviceability checked with factored loads.**

A complete combination set is not a long list for its own sake. It is the proof that every member has been checked against the case that can break it.

## Frequently asked questions

### Why is dead load factored by 0.9 in some combinations?

When dead load helps resist the effect being checked, such as wind uplift or overturning, a lower factor is used because overestimating the dead load would be unsafe. IS 800 Table 4 gives 0.9 for dead load where it is favourable.

### Are wind and earthquake combined together?

No. Wind and seismic loads are not assumed to act at the same time. Each is combined separately with dead, imposed and crane loads.

### How many load combinations does a typical PEB have?

It depends on the number of wind directions, internal pressure cases, crane positions and seismic directions. A crane building can easily have many dozens of combinations. The number is not the goal; covering every governing case is.

### Do serviceability checks use the same combinations?

No. Deflection and drift are checked under unfactored loads in separate serviceability combinations, with load factors of one.