title: "IS 1893 seismic load for PEB: a practical guide"
description: "How to apply IS 1893 (Part 1):2016 to pre-engineered buildings: zone factor, importance factor, response reduction, seismic weight and when wind governs."
url: https://ganithva.com/blog/is-1893-seismic-load-for-peb
---

# IS 1893 seismic load for PEB: zone, importance, R and seismic weight

A PEB is light, so its seismic force is often small. Small is not zero, and the way you set up the seismic case still decides bracing, anchor bolts and detailing.

16 NOVEMBER 2026 · 7 MIN READ

**Key points**

- IS 1893 (Part 1):2016 gives the design horizontal seismic coefficient for a PEB as Ah = (Z / 2) × (I / R) × (Sa / g), and the base shear is Ah multiplied by the seismic weight.
- IS 1893 zone factors are 0.10 for Zone II, 0.16 for Zone III, 0.24 for Zone IV and 0.36 for Zone V; most warehouses and factory sheds take an importance factor of 1.0.
- For a PEB portal frame the response reduction factor R is earned by detailing: a tapered frame without special seismic detailing is an ordinary moment frame and takes the lower R value.
- PEB seismic weight includes the full dead load and permanent collateral loads such as services, sprinklers, false ceilings and solar panels, while IS 1893 allows the roof imposed load to be left out.
- Wind usually governs a light metal-clad PEB, but seismic can govern with heavy collateral loads, mezzanines, cranes, masonry walls or a high zone with low wind, and often governs longitudinal bracing.

Every pre-engineered building in India must be checked for earthquake load to **IS 1893 (Part 1):2016**. For most single-storey sheds the seismic force turns out smaller than the wind force, and many designers stop thinking about it after the first run. That is a mistake. The seismic case still controls the longitudinal bracing on many jobs, it decides how anchor bolts and base plates are detailed, and it becomes critical as soon as the building carries something heavy.

This post walks through the inputs one at a time, in the order you set them up.

## The design horizontal seismic coefficient

IS 1893 uses the equivalent static method for regular, low-rise buildings such as PEBs. The design horizontal seismic coefficient is:

**Ah = (Z / 2) × (I / R) × (Sa / g)**

The base shear is Ah multiplied by the seismic weight of the building. Each term deserves a short look.

### Zone factor Z

India is divided into four seismic zones. The zone factor is the expected peak ground acceleration as a fraction of g:

| Zone | Zone factor Z | Typical description |

| II | 0.10 | Low seismic intensity |

| III | 0.16 | Moderate |

| IV | 0.24 | Severe |

| V | 0.36 | Very severe |

Read the zone from the map and the town list in the code, not from memory. Industrial belts near zone boundaries are common, and a site one zone higher changes the force by a large ratio.

### Importance factor I

The importance factor raises the force for buildings that must stay usable after an earthquake or that hold many people. Most warehouses and factory sheds take the base value of 1.0. Higher values apply to critical and lifeline structures and to buildings with high occupancy. If the client is a hospital, a power plant, an emergency facility or a school, ask before assuming 1.0.

### Response reduction factor R

R reflects how much the structure can yield and dissipate energy without collapse. For steel buildings IS 1893 gives separate values for ordinary and special moment-resisting frames and for different types of braced frames.

The key point for PEBs: **R is earned by detailing, not chosen**. A tapered portal frame with slender plate elements, bolted end-plate knees and no special seismic detailing is an ordinary moment frame, and it takes the lower R. Using the higher value for a special moment frame without meeting the ductile detailing rules in IS 800 understates the force.

In the longitudinal direction the lateral system is usually rod or angle bracing. Tension-only rod bracing has limited ductility, so check the R that applies to it and make sure the bracing connections are stronger than the members.

### Spectral acceleration Sa/g

Sa/g depends on the soil type and the fundamental natural period. For a steel moment frame, the code gives an empirical period formula based on building height (Ta = 0.085 h^0.75 for steel moment frames). A low PEB has a short period, which usually places it on the flat, maximum plateau of the response spectrum. In practice this means Sa/g is often at its peak value for PEBs, so do not expect the period to reduce the force much.

If you run a dynamic analysis, scale the result to the minimum base shear the code requires.

**IS 800:2026 note.** The 2026 edition of IS 800 lets regular single-storey industrial frames skip ductile detailing if they are designed with R = 1.5, and allows only special frames as ductile systems in zone III and above. See [IS 800:2026 vs IS 800:2007](https://ganithva.com/blog/is-800-2026-what-changes-for-peb).

## Seismic weight: what goes in

The seismic weight is the load that the earthquake shakes. For a PEB it includes:

- **Full dead load**: frames, purlins, girts, bracing, sheeting, insulation, skylights.

- **Collateral dead load**: services, sprinkler pipes, cable trays, false ceiling, ducts, solar panels. These are permanent and must be counted.

- **Imposed load on floors** such as mezzanines, at the fraction the code specifies for that load intensity.

- **Crane self-weight**: include the bridge and crab. Handle the lifted load as the code and the project design basis direct; it is usually not added to the seismic weight because a hanging load does not move rigidly with the frame.

- **Wall weight**: if the lower part of the wall is brick or block masonry tied to the columns, the tributary wall weight adds to the seismic mass.

The roof imposed load can be left out of the seismic weight. This is one reason the seismic case is light for a plain warehouse roof: the main live load on the roof simply does not count.

For more on what goes into dead and collateral load, see our post on [dead, live and collateral loads on a PEB roof](https://ganithva.com/blog/dead-live-and-collateral-loads-peb-roof).

## When wind governs and when seismic governs

A PEB with metal roof and walls has a low weight per square metre of roof but a large surface exposed to wind. Wind force scales with area; seismic force scales with mass. That is why, for a light, open warehouse, wind usually governs the main frames, the purlins and the girts.

Seismic starts to matter when the mass goes up or the wind goes down:

- **Heavy collateral loads**: solar panels, large ducts, process piping hung from the roof.

- **Mezzanine floors** inside the PEB.

- **Overhead cranes**, where the bridge weight sits high on the column.

- **Masonry walls** up to a dado or full height.

- **High seismic zone with low basic wind speed**, a combination found in parts of the north and north-east.

- **Longitudinal direction**: the end-wall wind force is small, so seismic often governs the roof and wall bracing even when wind governs the frames.

Do not decide this by judgement. Run both cases through the load combinations and let the checks tell you. Our [IS 875 Part 3 wind load guide](https://ganithva.com/guides/is-875-part-3-wind-load-peb) covers the wind side of the comparison.

## Combining seismic with other loads

IS 800 Table 4 and IS 1893 give the limit state combinations with seismic load. Wind and earthquake are never applied together. The seismic force is applied along each principal direction, and the code requires combining the two horizontal directions (full force in one direction with a fraction of it in the other) when the structure is not symmetric or when members resist force from both directions, such as corner columns and base plates.

The case with reduced dead load and seismic is the one that pulls hardest on anchor bolts, so do not skip it. See [load combinations for PEB to IS 800](https://ganithva.com/blog/load-combinations-for-peb-is-800) for the full set.

## Detailing points that follow from the seismic case

- **Bracing connections** should be designed for the strength of the brace, not just the computed force, so that the brace yields before the bolt or gusset fails.

- **Anchor bolts and base plates** must resist the uplift and shear from the seismic case with reduced dead load.

- **Masonry walls** need a movement joint or flexible ties at the steel column so they do not attack the frame or fall out of plane.

- **Mezzanines** connected to the main frame add mass and stiffness at an intermediate level; model them, do not treat them as separate.

- **Drift** under seismic load must stay within the code limit, and cladding must tolerate it.

## A short checklist

- Confirm the zone, soil type and importance factor with the client.

- Pick R for the lateral system you will actually detail in each direction.

- List every permanent load that adds mass, including services and panels.

- Compute base shear in both directions and distribute it to frames and bracing.

- Run all seismic combinations alongside wind and compare.

- Detail bracing, connections and anchors for the governing case.

Software can set up these cases for you; Ganithva, for example, generates IS 875 and IS 1893 load cases and runs IS 800 checks on them. The engineer still decides the zone, the importance factor and the R value, and signs the result.

## Frequently asked questions

### Does seismic load ever govern a PEB design?

It can. For a bare warehouse with metal sheeting, wind usually governs the main frames. Seismic can govern when the building carries heavy collateral loads, a mezzanine, cranes, solar panels or masonry walls, or when it sits in Zone IV or V in a low-wind region.

### Which response reduction factor should I use for a PEB portal frame?

Use the value IS 1893 (Part 1):2016 gives for the lateral system you actually provide and detail. A portal frame designed as an ordinary moment frame takes the lower value; a higher value is only valid if the frame meets the ductile detailing rules for that system in IS 800.

### Is the roof live load included in the seismic weight?

IS 1893 (Part 1) allows the imposed load on the roof to be left out of the seismic weight. Permanent collateral loads such as services, sprinklers, false ceilings and solar panels are part of the dead load and must be included.

### Do I need to check seismic in both directions?

Yes. Check the transverse direction, where the portal frames resist the force, and the longitudinal direction, where wall and roof bracing carry it. Combine the two directions as the code requires.